Violation Detail
Standard Cited: 19100119 J04 IV Process safety management of highly hazardous chemicals.
Inspection Nr: 1461749.015
Citation: 01004D
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/06/2020
Nr Instances: 2
Nr Exposed: 500
Abatement Date: 07/30/2020
Gravity: 10
Report ID: 1032500
Contest Date: 07/29/2020
Final Order: 04/07/2021
Related Event Code (REC): C
Emphasis:
Substance: 0640
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/07/2021 | $0.00 | 07/30/2020 | Serious | |
Penalty | C: Contested | 08/05/2020 | $0.00 | 07/30/2020 | Serious | |
Penalty | Z: Issued | 07/06/2020 | $0.00 | 07/30/2020 | Serious |
Text For Citation: 01 Item/Group: 004D Hazard:
29 CFR 1910.119(j)(4)(iv): The employer did not document each inspection and test that was performed on process equipment wherein the documentation identified the date of the inspection or test, the name of the person who performed the inspection or test, the serial number or other identifier of the equipment on which the inspection or test was performed, a description of the inspection or test performed, and the results of the inspection or test. (a) Lurgi Plant: The employer did not document the results of chlorine area monitor calibrations. (b) Lurgi Plant: The employer did not document inspection and preventative maintenance for valve HCV 5145. Note: Abatement documentation and certification are required for this item.