Violation Detail
Standard Cited: 19100307 C02 I Hazardous (classified) locations.
Inspection Nr: 1650317.015
Citation: 01004C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,938.00
Current Penalty: $0.00
Issuance Date: 08/09/2023
Nr Instances: 2
Nr Exposed: 65
Abatement Date: 01/02/2024
Gravity: 10
Report ID: 0111400
Contest Date:
Final Order: 09/01/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/01/2023 | $0.00 | 01/02/2024 | Serious | |
| Penalty | Z: Issued | 08/09/2023 | $10,938.00 | 09/28/2023 | Serious |
Text For Citation: 01 Item/Group: 004C Hazard:
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the class of location: Facility: In the following locations, electrical equipment in hazardous locations was not approved for the class of location: Roof Booth: The electrical box located just outside the Roof Booth where fiberglass lay-up operations occurred was not rated to prevent the entry and accumulation of flammable vapors inside the box and onto unprotected electrical components. Because of these conditions, this location is considered a Class I, Division 1 location; Cutting Booth: The electrical box located just outside of the booth were not rated to prevent the accumulation of combustible dusts inside the box and onto unprotected electrical components. Because of these conditions this location is considered a Class II, Division 2 location;