Violation Detail
Standard Cited: 19100119 J04 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1782128.015
Citation: 01004B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/14/2025
Nr Instances: 3
Nr Exposed: 7
Abatement Date: 05/30/2025
Gravity: 5
Report ID: 0626600
Contest Date:
Final Order: 05/14/2025
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/14/2025 | $0.00 | 05/30/2025 | Serious | |
Penalty | Z: Issued | 04/14/2025 | $0.00 | 05/30/2025 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.119(j)(4)(ii): Inspection and testing procedures did not follow recognized and generally accepted good engineering practices: (a) On October 16, 2024, and at times prior, at the RapidXchange facility in Brookshire, Texas, the employer did not follow Recognized and Generally Acceptable Good Engineering Practices (RAGAGEP) such as but not limited to, API 510 Pressure Vessel Inspection Code: In-service Inspection, Rating, Repair, and Alteration, (2014) section 9.3.4 for external inspections, when they failed to perform an adequate inspection on Pressure Vessel tank #1 containing 59,220 lbs. of propane. (b) On October 16, 2024, and at times prior, at the RapidXchange facility in Brookshire, Texas, the employer did not follow Recognized and Generally Acceptable Good Engineering Practices (RAGAGEP) such as but not limited to, API 510 Pressure Vessel Inspection Code: In-service Inspection, Rating, Repair, and Alteration, (2014) section 9.3.4 for external inspections, when they failed to perform an adequate inspection on Pressure Vessel tank #2 containing 88,992 lbs. of Propane. (c) On October 16, 2024, and at times prior, at the RapidXchange facility in Brookshire, Texas, the employer did not follow Recognized and Generally Acceptable Good Engineering Practices (RAGAGEP) such as but not limited to, API 570 Piping Inspection Code: In-service Inspection, Rating, Repair, and Alteration of Piping Systems (2016) section 6.4 for Visual External Inspections, when it failed to perform adequate inspection on the process piping connected to pressure vessels containing propane.