Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1768502.015
Citation: 01004B
Citation Type: Other
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 02/05/2025
Nr Instances: 4
Nr Exposed: 1
Abatement Date: 03/04/2025
Gravity: 10
Report ID: 0317300
Contest Date: 03/04/2025
Final Order: 09/05/2025
Related Event Code (REC):
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 09/05/2025 | $0.00 | 03/04/2025 | Other | |
Penalty | C: Contested | 03/05/2025 | $0.00 | 03/04/2025 | Serious | |
Penalty | Z: Issued | 02/05/2025 | $0.00 | 03/04/2025 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. a) 1000 CenterPoint Blvd., New Castle, DE 19720 (OCC-1 Compressor Thermosyphon Oil Cooler/Shell and Tube Heat Exchanger) On or about August 15, 2024, the employer did not document that equipment complied with their chosen Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) ANSI/ASHRAE STANDARD 15 -1989 Safety Code for Mechanical Refrigeration section 9.1.6 when the employer failed to ensure liquid ammonia and/or oil from relief devices were directed to a safe location. Failure to install relief devices in the proper locations could result in an employee's exposure to vapor or liquid ammonia resulting in serious injury. b) 1000 CenterPoint Blvd., New Castle, DE 19720 (OCC-2 Compressor Thermosyphon Oil Cooler/Shell and Tube Heat Exchanger) On or about August 15, 2024, the employer did not document that equipment complied with their chosen Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) ANSI/ASHRAE STANDARD 15 -1989 Safety Code for Mechanical Refrigeration section 9.1.6 when the employer failed to ensure liquid ammonia and/or oil from relief devices were directed to a safe location. Failure to install relief devices in the proper locations could result in an employee's exposure to vapor or liquid ammonia resulting in serious injury. c) 1000 CenterPoint Blvd., New Castle, DE 19720 (OCC-3 Compressor Thermosyphon Oil Cooler/Shell and Tube Heat Exchanger) On or about August 15, 2024, the employer did not document that equipment complied with their chosen Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) ANSI/ASHRAE STANDARD 15 -1989 Safety Code for Mechanical Refrigeration section 9.1.6 when the employer failed to ensure liquid ammonia and/or oil from relief devices were directed to a safe location. Failure to install relief devices in the proper locations could result in an employee's exposure to vapor or liquid ammonia resulting in serious injury. d) 1000 CenterPoint Blvd., New Castle, DE 19720 (Rooftop-Relief Header/diffuser): On or about August 15, 2024, The employer did not document that the equipment complies with section Appendix A section Diffuser B .7 (pg 20) of ANSI/ASHRAE STANDARD 15 -1989 Safety Code for Mechanical Refrigeration when the employer did not ensure the rooftop diffuser design complied with section 9.4.8 which states the discharge termination shall be fashioned in such a manner to prevent direct spray discharge refrigerated on personnel in the vicinity. This hazardous condition exposed employees accessing/egressing from the roof using the fixed ladder system to severe injury due to the potential of fire and toxic chemical overexposure hazards during an anhydrous ammonia relief discharge event.