Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1749070.015
Citation: 01004B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/25/2024
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 11/06/2024
Gravity: 5
Report ID: 0521400
Contest Date: 11/18/2024
Final Order: 02/27/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 02/27/2025 | $0.00 | 11/06/2024 | Other | |
| Penalty | C: Contested | 11/18/2024 | $0.00 | 11/06/2024 | Serious | |
| Penalty | Z: Issued | 10/25/2024 | $0.00 | 11/06/2024 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: (a) Spray Finishing Department - On or about May 16, 2024, employees were exposed to fire hazards. Electrical wiring and equipment such as electrical cords, a Skyjack Electric Lift (Model SJIII-3219 / SN: 227462), fans, and portable drills were not explosion-proof type approved. Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.13(c).
Translate