Violation Detail
Standard Cited: 19100107 D12 Spray finishing using flammable and combustible materials.
Inspection Nr: 1683497.015
Citation: 01004B
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/28/2023
Nr Instances: 1
Nr Exposed: 4
Abatement Date:
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 10/24/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/24/2023 | $0.00 | Other | ||
Penalty | Z: Issued | 09/28/2023 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.107(d)(12): Freshly sprayed articles were dried in spaces that were not provided with adequate ventilation to prevent the formation of explosive vapors. When adequate and reliable ventilation was not provided such drying spaces were considered a spraying area, for the purposes of this standard: Spray Finishing Area: On, or about, July 20, 2023, freshly sprayed items passed wall mounted electrical controls for the drying oven that were not rated for use in a Class 1 location. The stains and coatings that were applied were Category 2 and 3 flammable liquids.