Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 1682467.015
Citation: 01004B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/28/2023
Nr Instances: 3
Nr Exposed: 3
Abatement Date: 08/09/2023
Gravity: 5
Report ID: 0936200
Contest Date:
Final Order: 08/28/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/28/2023 | $0.00 | 08/09/2023 | Serious | |
| Penalty | Z: Issued | 07/28/2023 | $0.00 | 08/09/2023 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On and/or before July 11, 2023, the employer used extension cords and surge protectors to power various pieces of equipment. This condition potentially exposed employee(s) to electrical shock and/or fire hazard(s). In the following locations: a) Laundry room two extension cords were spliced together and one end terminated in an outlet box. The outlet box was powering an Amana air conditioner unit. b) Laundry room two ends of an extension cord were cut and tied into the hot water heater circulation pump system. c) Lobby storage room had an extension cord plugged into a surge protector to power a microwave and coffee maker.