Violation Detail
Standard Cited: 19100305 G01 IV A Wiring methods, components, and equipment for general use.
Inspection Nr: 1472516.015
Citation: 01004B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/06/2020
Nr Instances: 3
Nr Exposed: 3
Abatement Date: 10/28/2020
Gravity: 5
Report ID: 0627100
Contest Date:
Final Order: 10/28/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/28/2020 | $0.00 | 10/28/2020 | Serious | |
| Penalty | Z: Issued | 10/06/2020 | $0.00 | 10/28/2020 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: On or about April 20, 2020, employees operating the off-bear-belt and edger machine were exposed to fire and electric shock hazards from flexible cords used to provide power to equipment such as, but not limited to: (a) Off-bear station foot pedals (b) Edger control board receiving power from yellow cord connect to switch mounted to disconnect (c) Electrical panels and disconnects located on the wall behind the off-bear conveyor (d)