Violation Detail
Standard Cited: 19100107 D07 Spray finishing using flammable and combustible materials.
Inspection Nr: 1441449.015
Citation: 01004B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/20/2020
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 07/10/2020
Gravity: 5
Report ID: 0627700
Contest Date:
Final Order: 05/11/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/11/2020 | $0.00 | 07/10/2020 | Serious | |
Penalty | Z: Issued | 04/20/2020 | $0.00 | 05/12/2020 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.107(d)(7): Exhaust ducts were not constructed of steel. On or about October 29, 2019, Powder Shop, the employer did not ensure that the exhaust ducts for two cabinet spray booths were constructed of steel. The exhaust ducts for the two cabinet spray booths were constructed of flexible aluminum duct. Employees sprayed powder (combustible dust) at cabinet spray booths and were exposed to fire and explosion hazards.