Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1116536.015
Citation: 01004B
Citation Type: Serious
Abatement Date: 10/13/2017 4
Initial Penalty: $3,500.00
Current Penalty: $0.00
Issuance Date: 06/30/2016
Nr Instances: 2
Nr Exposed: 3
Related Event Code (REC):
Gravity: 5
Report ID: 0524530
Contest Date: 07/14/2016
Final Order: 10/13/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 10/13/2017 | $0.00 | 10/13/2017 | Serious | |
Penalty | C: Contested | 07/15/2016 | $3,500.00 | 07/13/2016 | Serious | |
Penalty | Z: Issued | 06/30/2016 | $3,500.00 | 07/13/2016 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed. The employer failed to ensure that wires entering the breaker panel, located on the stairs at the north wall, were protected from abrasion when: A. Wires were connected to the breaker panel and ran into the front of the box. B. Wires ran into the box thorough unprotected cutouts.