Violation Detail
Standard Cited: 19100107 C05 Spray finishing using flammable and combustible materials.
Inspection Nr: 1076208.015
Citation: 01004B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/16/2015
Nr Instances: 3
Nr Exposed: 16
Abatement Date: 10/13/2015
Gravity: 1
Report ID: 0419700
Contest Date:
Final Order: 10/08/2015
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/08/2015 | $0.00 | 10/13/2015 | Serious | |
Penalty | Z: Issued | 09/16/2015 | $0.00 | 10/13/2015 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.107(c)(5): Combustible residues, areas. Unless specifically approved for locations containing both deposits of readily ignitable residue and explosive vapors, there shall be no electrical equipment in any spraying area, whereon deposits of combustible residues may readily accumulate, except wiring in rigid conduit or in boxes or fittings containing no taps, splices, or terminal connections. A). On or about July 8, 2015 employees were exposed to explosion and burn injuries because they were completing paint spraying tasks in an area where ignitable residues and explosive vapors were present with non approved electrical equipment and flexible wires. The exhaust fan used for mechanical ventilation was not an approved explosion proof piece of equipment. The wiring for the device were not contained in rigid conduit and were taped and spliced to extend the wires reach to an outlet.