Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1071653.015
Citation: 01004B
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/10/2015
Nr Instances: 1
Nr Exposed: 1
Abatement Date:
Gravity: 5
Report ID: 0523400
Contest Date:
Final Order: 10/09/2015
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/09/2015 | $0.00 | Serious | ||
| Penalty | Z: Issued | 09/10/2015 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 004B Hazard:
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater : (a) The employer did not ensure that the clearance width was maintained in front of an electrical panel on the north wall in the shop area.
Translate