Violation Detail
Standard Cited: 19100303 G01 II General.
Inspection Nr: 928043.015
Citation: 01004A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,295.00
Current Penalty: $1,494.00
Issuance Date: 10/28/2013
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 11/12/2013
Gravity: 1
Report ID: 0213400
Contest Date:
Final Order: 11/18/2013
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 11/18/2013 | $1,494.00 | 11/12/2013 | Serious | |
| Penalty | Z: Issued | 10/28/2013 | $2,295.00 | 11/12/2013 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.303(g)(1)(ii): Working space provided about electrical equipment rated 600 volts, nominal, or less was used for storage: a/ RRE Operations/Raritan NJ Site 1/ Dietary/Kitchen Area Electrical panel and junction boxes located in a closet type room: The room was filled with storage, blocking the electrical equipment 2/ Boiler Room Main Electrical Power: The electrical panels were blocked by a portable "Central Pneumatic" air compressor. Electrical panels and junction boxes (voltage 480 Volts/3 phase) were not maintained free of storage material/equipment to allow for a minimum 30 inches of working space. Observed on/or about 8/9/2013.