Violation Detail
Standard Cited: 19100119 J04 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1800723.015
Citation: 01004A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,093.00
Current Penalty: $7,093.00
Issuance Date: 07/18/2025
Nr Instances: 3
Nr Exposed: 12
Abatement Date: 09/04/2025
Gravity: 1
Report ID: 0625500
Contest Date:
Final Order: 08/12/2025
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/12/2025 | $7,093.00 | 09/04/2025 | Serious | |
Penalty | Z: Issued | 07/18/2025 | $7,093.00 | 09/04/2025 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.119(j)(4)(ii): Inspection and testing procedures did not follow recognized and generally accepted good engineering practices (RAGAGEP). On or about 1/29/2025, at the Lubrizol facility, corrosion rates for listed piping segments were not established in accordance with recognized and generally accepted good engineering practices (RAGAGEP) such as America Petroleum Institute (API) Standard 570 - 2009 (Piping Inspection Code: In-service Inspection, Rating, Repair, and Alteration of Piping Systems), Section 7.1.3 "Existing Piping Systems" for: a) Isopropyl alcohol (IPL) outlet line, P-2"-115-SS, from TK-120 through pump P-120 to product header (600-PID-00XX Rev. B). b) Methanol (MAOL) outlet line, P-3"-143-316-SS, from TK-116 to the product header (100-PID-0016 Rev. A). c) Formaldehyde outlet line, P-2"-106-SS, from TK-101 through pump P-101 to the product header (100-PID-0001 Rev. B).