Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
This violation item has been deleted.
Inspection Nr: 1800699.015
Citation: 01004A
Citation Type: Serious
Abatement Status:
Initial Penalty: $6,620.00
Current Penalty: $0.00
Issuance Date: 04/22/2025
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 05/16/2025
Gravity: 5
Report ID: 0522300
Contest Date:
Final Order: 05/08/2025
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/08/2025 | $0.00 | 05/16/2025 | Serious | |
Penalty | Z: Issued | 04/22/2025 | $6,620.00 | 05/16/2025 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spray area, and not separated therefrom by partitions, produced sparks under normal operating conditions and did not otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations: On or about January 29, 2025, the employer failed to ensure that electrical wiring within 20 feet of a spray area did not produce sparks and otherwise conformed to the provisions of subpart S for Class I, Division 2 Hazardous Locations when several outlets and light switches were hanging right outside a spray booth when employees spray 3M Scotch-Weld Epoxy Adhesive 2214 Regular mixed with Klean Strip Lacquer Thinner onto parts.