Violation Detail
Standard Cited: 19100107 B10 Spray finishing using flammable and combustible materials.
Inspection Nr: 1749070.015
Citation: 01004A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,067.00
Current Penalty: $8,067.00
Issuance Date: 10/25/2024
Nr Instances: 2
Nr Exposed: 2
Abatement Date: 11/06/2024
Gravity: 5
Report ID: 0521400
Contest Date: 11/18/2024
Final Order: 02/27/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 02/27/2025 | $8,067.00 | 11/06/2024 | Serious | |
| Penalty | C: Contested | 11/18/2024 | $8,067.00 | 11/06/2024 | Serious | |
| Penalty | Z: Issued | 10/25/2024 | $8,067.00 | 11/06/2024 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.107(b)(10): Illumination panels did not effectively isolate the spraying area from the area in which the lighting unit is located. (a) Spray Finishing Department, Cross-Draft Booth Booths - On or about May 23, 2024, employees were exposed to fire hazards. The top enclosures of the lighting unit were not secured, subjecting the lamps to contact with flammable material. (b) Spray Finishing Department, Downdraft Booth - On or about May 23, 2024, employees were exposed to fire hazards. Enclosures of lighting units were not secured, broken, or missing, subjecting the lamps to contact with flammable material. Abatement certification is required of this item in accordance with the requirements of 29 CFR 1903.13(c).