Violation Detail
Standard Cited: 19100303 G01 General.
Inspection Nr: 1690819.015
Citation: 01004A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,050.00
Current Penalty: $6,630.00
Issuance Date: 11/24/2023
Nr Instances: 3
Nr Exposed: 5
Abatement Date: 12/05/2023
Gravity: 5
Report ID: 0524500
Contest Date:
Final Order: 12/20/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/20/2023 | $6,630.00 | 12/05/2023 | Serious | |
Penalty | Z: Issued | 11/24/2023 | $11,050.00 | 12/05/2023 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: On or about August 14, 2023, employees were exposed to electrical hazards because there was insufficient access provided to the: a. electrical panel located in the Roll Room. b. electrical disconnects located on the north wall in the Small Parts Room. c. electrical panel and disconnects in the Warehouse.