Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
Inspection Nr: 1594208.015
Citation: 01004A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $14,502.00
Current Penalty: $7,251.00
Issuance Date: 09/06/2022
Nr Instances: 6
Nr Exposed: 9
Abatement Date: 01/03/2023
Gravity: 10
Report ID: 0625400
Contest Date:
Final Order: 09/30/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/30/2022 | $7,251.00 | 01/03/2023 | Serious | |
Penalty | Z: Issued | 09/06/2022 | $14,502.00 | 10/24/2022 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.119(j)(4)(i): Inspections and tests were not performed on process equipment. On or about May 4, 2022, the employer did not perform inspections and tests on process equipment including but not limited to the following piping circuits: a. 8"-HC-2030-3"H-B1(P-202 Crude Booster Pump discharge). P&ID M-02. b. 8"-HC-2178-3 ?"H-B1 (P-202 Crude Booster Pump suction). P&ID M-02. c. 3"-HC-2005-N-A1 (P-203A/B discharge line). P&ID M-06. d. 3"-HC-3011-1 ?"-A1 (C-301 Overhead). P&ID M-07. e. 4"-HC-3036-4"H-B1 (C-301 bottom to E-302), P&ID M-07 and f. 8"-HC-3031-3"H-B1 (E-307 Overhead to C-302). P&ID M-09