Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1543751.015
Citation: 01004A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/14/2022
Nr Instances: 1
Nr Exposed: 10
Abatement Date: 02/03/2022
Gravity: 5
Report ID: 0627100
Contest Date:
Final Order: 02/10/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/10/2022 | $0.00 | 02/03/2022 | Serious | |
Penalty | Z: Issued | 01/14/2022 | $0.00 | 02/03/2022 | Serious |
Text For Citation: 01 Item/Group: 004A Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: On Blower #2, employees were exposed to electric shock hazards in that the flexible metallic conduit entering the junction box on the duct is separated from the bushing, exposing the insulated conductors.