Violation Detail
Standard Cited: 19100304 G06 VI C 5 Wiring design and protection.
Inspection Nr: 996693.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,930.00
Current Penalty: $6,390.00
Issuance Date: 03/20/2015
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 03/26/2015
Gravity: 10
Report ID: 0420600
Contest Date: 04/13/2015
Final Order: 12/31/2015
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | J: ALJ Decision | 12/31/2015 | $6,390.00 | 03/26/2015 | Serious | |
| Penalty | C: Contested | 04/15/2015 | $6,930.00 | 03/26/2015 | Serious | |
| Penalty | Z: Issued | 03/20/2015 | $6,930.00 | 03/26/2015 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.304(g)(6)(vi)(C)(5): The employer did not ensure that exposed noncurrent-carrying metal parts of cord-and-plug connected equipment that may become energized was grounded when the equipment was used in damp or wet locations by employees standing on the ground. a) For employees working at 5127 Bloomingdale Avenue in Tampa, as observed on or about 24 September, 2014. Employees were using 2 wire non grounded handheld lamps. the lamp cord was repaired and the polarity was reversed. Employee was in the process of changing the light bulb inside of one of the metal archways when contact was made with the metal casing that was energized and employee was electrocuted.