Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
Inspection Nr: 975505.015
Citation: 01004
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $4,500.00
Current Penalty: $2,700.00
Issuance Date: 09/26/2014
Nr Instances: 1
Nr Exposed: 15
Abatement Date:
Gravity: 5
Report ID: 0213600
Contest Date:
Final Order: 10/10/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/10/2014 | $2,700.00 | Serious | ||
| Penalty | Z: Issued | 09/26/2014 | $4,500.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment a) On or about 05/07/14 in the Engine Room; since installation, employer failed to conduct testing of the high level alarm on accumulators, such as but not limited to #1, #2, #3, and 1851 compressor accumulator, required by Section 6.6.4 of the International Institute of Ammonia Refrigeration (IIAR) Bulletin 110, 3/93; which established annual testing. NO ABATEMENT CERTIFICATION REQUIRED