Violation Detail
Standard Cited: 19100106 D04 II Flammable liquids.
This violation item has been deleted.
Inspection Nr: 893753.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,800.00
Current Penalty: $0.00
Issuance Date: 09/05/2013
Nr Instances: 1
Nr Exposed: 23
Abatement Date: 12/09/2013
Gravity: 10
Report ID: 0521400
Contest Date: 09/26/2013
Final Order: 10/23/2014
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 10/23/2014 | $0.00 | 12/09/2013 | Serious | |
| Penalty | C: Contested | 11/18/2013 | $2,800.00 | 12/09/2013 | Serious | |
| Penalty | Z: Issued | 09/05/2013 | $2,800.00 | 12/09/2013 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.106(d)(4)(ii): "Rating and capacity." Storage in inside storage rooms shall comply with Table H-13: On or about March 6, 2013, Fox Valley Systems, Inc., stored flammable material in the raw material storage warehouse in excess of the maximum allowed by Table H-13. Table H-13 allows a maximum storage area of 500 square feet and a maximum allowable quantity of 10 gallons per square foot of floor area. The employer stored more than 10,000 gallons of flammable and combustible material, and the area of the warehouse was 9,472 square feet. DOCUMENTATION AND CERTIFICATION ARE REQUIRED FOR THIS ITEM.
Translate