Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1809050.015
Citation: 01004
Citation Type: Serious
Abatement Status:
Initial Penalty: $10,641.00
Current Penalty: $9,100.00
Issuance Date: 07/28/2025
Nr Instances: 2
Nr Exposed: 11
Abatement Date: 12/01/2025
Gravity: 5
Report ID: 0627700
Contest Date:
Final Order: 09/02/2025
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/02/2025 | $9,100.00 | 12/01/2025 | Serious | |
Penalty | Z: Issued | 07/28/2025 | $10,641.00 | 08/14/2025 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: a.) On or about March 6, 2025 and at times prior, in the north paint shop, explosion-proof approved lighting was not used in the spraying area during spraying operations. b.) On or about March 6, 2025 and at times prior, in the south paint shop, explosion-proof approved lighting was not used in the spraying area during spraying operations.