Violation Detail
Standard Cited: 19100335 A01 I Safeguards for personnel protection.
Inspection Nr: 1767969.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,005.00
Current Penalty: $13,005.00
Issuance Date: 02/03/2025
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 03/04/2025
Gravity: 5
Report ID: 0830600
Contest Date:
Final Order: 02/27/2025
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 02/03/2025 | $13,005.00 | 03/04/2025 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: (a) Rail mill electrical room: On or before August 9, 2024, and at times prior the employer did not ensure that maintenance electrical technicians wore appropriate electrical protective equipment when locking out energized 480-volt electrical circuits. Employees opened and closed a knife switch on the stamp wheel electrical panel (CP-6C) in close proximity to energized conductors without personal protective equipment such as an arc-rated face shield, arc-rated balaclava and voltage rated gloves. This condition exposed the employees to hazards such as shock, electrocution, arc blast, and arc flash.