Violation Detail
Standard Cited: 19100119 J04 III Process safety management of highly hazardous chemicals.
Inspection Nr: 1741099.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $16,131.00
Current Penalty: $16,131.00
Issuance Date: 07/16/2024
Nr Instances: 1
Nr Exposed: 8
Abatement Date: 09/04/2024
Gravity: 10
Report ID: 0627510
Contest Date: 08/14/2024
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | C: Contested | 08/21/2024 | $16,131.00 | 09/04/2024 | Serious | |
| Penalty | Z: Issued | 07/16/2024 | $16,131.00 | 09/04/2024 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience. On or about April 10, 2024, in the Main ammonia engine room, the employer did not ensure dual relief valves on Low Stage Suction Accumulator (LSSA) were replaced and/or recertified according to their employed RAGAGEP including but not limited to IIAR Bulletin 110 (Start Up, Inspection and Maintenance of Ammonia Mechanical Refrigerating Systems).