Standard Cited: 19100028 B03 IV Duty to have fall protection and falling object protection.
Inspection Nr: 1657904.015
Citation: 01004
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $15,625.00
Current Penalty: $10,000.00
Issuance Date: 08/02/2023
Nr Instances: 4
Nr Exposed: 10
Abatement Date: 09/19/2023
Gravity: 10
Report ID: 0627700
Contest Date:
Final Order: 08/28/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/28/2023 | $10,000.00 | 09/19/2023 | Other | |
| Penalty | Z: Issued | 08/02/2023 | $15,625.00 | 09/19/2023 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.28(b)(3)(iv): The employer did not provide that each employee be protected from falling into a ladderway floor hole or ladderway platform hole by a guardrail system and toeboards erected on all exposed sides, except at the entrance to the hole, where a self-closing gate or an offset must be used. Instance a.) On or about 3/08/2023, at the facility located in Enid Oklahoma on the platform of the evaporative condenser 3 (EC-3) on the roof the building #1, employees monitoring and/or checking conditions of the evaporative condenser were exposed to a fall hazard of more than four feet where the ladderway platform hole was not equipped with a self-closing gate or an offset. Instance b.) On or about 6/21/2023, at the facility located in Enid Oklahoma on the platform of the evaporative condenser 1 (EC-1) on the roof the building #1, employees monitoring and/or checking conditions of the evaporative condenser were exposed to a fall hazard more than four feet where the ladderway platform hole was not equipped with a self-closing gate or an offset. Instance c.) On or about 6/21/2023, at the facility located in Enid Oklahoma on the platform of valve area in the machinery (engine) room of the ammonia refrigeration system, employees checking conditions of valves were exposed to a fall hazard more than four feet where the ladderway platform hole was not equipped with a self-closing gate or an offset. Instance d.) On or about 6/21/2023, at the facility located in Enid Oklahoma on the platform in the hydraulic room, employees monitoring and/or checking conditions of vessels were exposed to a fall hazard more than four feet where the ladderway platform hole was not equipped with a self-closing gate or an offset.
Translate