Violation Detail
Standard Cited: 19100304 F01 IV Wiring design and protection.
Inspection Nr: 1648133.015
Citation: 01004
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $4,687.00
Current Penalty: $0.00
Issuance Date: 04/20/2023
Nr Instances: 3
Nr Exposed: 6
Abatement Date: 05/16/2023
Gravity: 1
Report ID: 0830500
Contest Date:
Final Order: 05/17/2023
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/17/2023 | $0.00 | 05/16/2023 | Other | |
| Penalty | Z: Issued | 04/20/2023 | $4,687.00 | 05/16/2023 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: a) Warehouse, Untha Shredder Machine Area: On 02/02/2023, the employer exposed employees to potential shock and/or fire hazards, in that a homemade crane was placed approximately 24" or less in front of a bank of 480 volts electrical shut-off (On/Off) switches. This blocked access to the electrical shut-offs used to power the Untha Shredder machine, Bailer 2, etc. b) Warehouse, NGR Area: On 02/02/2023, the employer exposed employees to potential shock and/or fire hazards, in that bags of plastic and other plastic materials were placed in front of an 480 volt electrical shut-off and an electrical panel. This blocked access to the electrical shut-off and electrical panel used to power the NGR machine. c) Warehouse, near Pulverizer Area: On 02/02/2023, the employer exposed employees to potential shock and/or fire hazards, in that of old equipment on a wooden pallet and a hydraulic jack were placed approximately 26" or less in front of an electrical panel. This blocked access to the electrical panel used to power heaters and a bailer.
Translate