Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1647763.015
Citation: 01004
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $11,162.00
Current Penalty: $0.00
Issuance Date: 07/26/2023
Nr Instances: 1
Nr Exposed: 45
Abatement Date: 08/15/2024
Gravity: 5
Report ID: 0316700
Contest Date:
Final Order: 08/16/2023
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/16/2023 | $0.00 | 08/15/2024 | Other | |
Penalty | Z: Issued | 07/26/2023 | $11,162.00 | 08/09/2023 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a. ShotPeen dust collection - On or about February 2, 2023, the employer installed electrical equipment not rated for class II environments in that area where the dust collection system is housed, exposing employees to deflagration hazards. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.