Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1641717.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,366.00
Current Penalty: $4,000.00
Issuance Date: 04/18/2023
Nr Instances: 1
Nr Exposed: 8
Abatement Date: 05/12/2023
Gravity: 1
Report ID: 0111700
Contest Date: 05/11/2023
Final Order: 11/20/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 11/20/2023 | $4,000.00 | 05/12/2023 | Serious | |
Penalty | C: Contested | 05/12/2023 | $7,366.00 | 05/12/2023 | Serious | |
Penalty | Z: Issued | 04/18/2023 | $7,366.00 | 05/12/2023 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Location: shop area next to bay 5 On or about 1/4/2023, circuit breakers located in an electrical panel were not labeled or not labeled correctly. Three circuit breakers were not labeled and in the on position, and one breaker labeled for the bathroom was the feed for the shop lights.