Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1613373.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,046.00
Current Penalty: $7,032.20
Issuance Date: 02/06/2023
Nr Instances: 5
Nr Exposed: 20
Abatement Date: 03/24/2023
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 03/02/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/02/2023 | $7,032.20 | 03/24/2023 | Serious | |
Penalty | Z: Issued | 02/06/2023 | $10,046.00 | 03/24/2023 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Base Web Deck Area: On or about August 9, 2022, the following electrical equipment used during dumping, mixing, collecting, and cleaning operations was not intrinsically safe and approved for the hazardous Class II Division 1 combustible dust location: a) Y-Tron 1 and Y-Tron 2 hopper motors, Weg W22 NEMA motor (Model TE1BFOXON), that displayed a Class I Zone 2 rating. b) Dust collector motor, Baldor Reliance Super-E Motor CEM3613T. c) Unapproved Channel Lock portable vacuum cleaner (Model No. VBV1210). d) Receptacles and attachment plugs were not identified for the Class II Division 1 location.