Violation Detail
Standard Cited: 19100304 B04 II B Wiring design and protection.
Inspection Nr: 1577492.015
Citation: 01004
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $5,801.00
Current Penalty: $4,750.00
Issuance Date: 08/05/2022
Nr Instances: 1
Nr Exposed: 5
Abatement Date:
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 09/20/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/20/2022 | $4,750.00 | Serious | ||
Penalty | Z: Issued | 08/05/2022 | $5,801.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.304(b)(4)(ii)(B):Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4: NEW FIRING ROOM: On or about February 10, 2022, a Pelonis Model PSH700S Portable Heater Fan was plugged into a relocatable power tap. The heater draws 12.5 amps when operating. The relocatable power tap was rated for 15 Amps and therefore the maximum load allowed is 12 Amps according to Table S-1.