Violation Detail
Standard Cited: 19100305 E01 Wiring methods, components, and equipment for general use.
Inspection Nr: 1575357.015
Citation: 01004
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $8,287.00
Current Penalty: $4,640.00
Issuance Date: 07/08/2022
Nr Instances: 1
Nr Exposed: 6
Abatement Date:
Gravity: 5
Report ID: 0214500
Contest Date:
Final Order: 08/09/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/09/2022 | $4,640.00 | Other | ||
Penalty | Z: Issued | 07/08/2022 | $8,287.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panel-board enclosures in damp or wet locations shall be installed so as to prevent moisture or water from entering and accumulating within the enclosures and shall be mounted so there is at least 6.35-mm (0.25-in.) airspace between the enclosure and the wall or other supporting surface. However, nonmetallic enclosures may be installed without the airspace on a concrete, masonry, tile, or similar surface. The enclosures shall be weatherproof in wet locations. a) Second floor meat department: Outlet boxes in damp or wet locations were not installed to prevent moisture and water from entering and accumulating within the enclosures, on or about 1/25/22.