Violation Detail
Standard Cited: 19100305 E01 Wiring methods, components, and equipment for general use.
Inspection Nr: 1548732.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $14,502.00
Current Penalty: $8,701.20
Issuance Date: 02/10/2022
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 03/02/2022
Gravity: 10
Report ID: 0317000
Contest Date:
Final Order: 03/14/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/14/2022 | $8,701.20 | 03/02/2022 | Serious | |
Penalty | Z: Issued | 02/10/2022 | $14,502.00 | 03/02/2022 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: (a) Jobsite located at 390 Boot Rd, West Chester, PA: Employees performing work inside the sprinkler room of Bldg. 104 (Learning Center) were exposed to electric shock hazards in that condensation from an overhead water pipe was dripping down and accumulating onto the electrical control panel of a Weil-McLain natural gas boiler, model no. LGB-11. Condition noted on or about the 6-month period of Feb 17 - August 17, 2021.