Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1547420.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,516.00
Current Penalty: $12,500.00
Issuance Date: 12/08/2021
Nr Instances: 2
Nr Exposed: 20
Abatement Date: 12/28/2021
Gravity: 10
Report ID: 0418600
Contest Date:
Final Order: 01/04/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/04/2022 | $12,500.00 | 12/28/2021 | Serious | |
Penalty | Z: Issued | 12/08/2021 | $13,516.00 | 12/28/2021 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Production area line 1; On or about August 10, 2021 and at times prior, the employer exposed employees to electrical hazards in that employees were required to use a 120 VAC electrical outlet constructed from a 4 " x 4" metal box with pre-punched knockouts on a flexible cord that was not listed or labeled for that use. b) Production area line 2; On or about August 10, 2021 and at times prior, the employer exposed employees to electrical hazards in that employees were required to use a 120 VAC electrical outlet constructed from a 4 " x 4" metal box with pre-punched knockouts on a flexible cord that was not listed or labeled for that use.