Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1532217.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $5,000.00
Issuance Date: 11/05/2021
Nr Instances: 3
Nr Exposed: 220
Abatement Date: 03/30/2022
Gravity: 5
Report ID: 0830500
Contest Date:
Final Order: 12/03/2021
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/03/2021 | $5,000.00 | 03/30/2022 | Serious | |
Penalty | Z: Issued | 11/05/2021 | $0.00 | 01/10/2022 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices: (a) Protein for Pets Opco, LLC, dba All American Pet Proteins, at 259 30th Street, Greeley, CO: On and preceding 9/3/2021, the employer did not document that equipment complies with recognized and generally accepted good engineering practices. Employees operated and maintained an ammonia refrigeration system. The refrigeration system contained approximately 12,700 pounds of ammonia. Ammonia is in the liquid phase during a portion of the refrigeration cycle. The engine room contained an emergency eyewash, but did not contain an emergency shower. This condition exposed employees to a corrosive liquid hazard. (b) Protein for Pets Opco, LLC, dba All American Pet Proteins, at 259 30th Street, Greeley, CO: On and preceding 9/3/2021, the employer did not document that equipment complies with recognized and generally accepted good engineering practices. Employees operated and maintained an ammonia refrigeration system. The refrigeration system contained approximately 12,700 pounds of ammonia. Ammonia is in the liquid phase during a portion of the refrigeration cycle. The emergency eyewash and shower outside the engine room were blocked by PVC piping. This condition exposed employees to a corrosive liquid hazard. (c) Protein for Pets Opco, LLC, dba All American Pet Proteins, at 259 30th Street, Greeley, CO: On and preceding 9/3/2021, the employer did not document that equipment complies with recognized and generally accepted good engineering practices. Employees operated and maintained an ammonia refrigeration system. The refrigeration system contained approximately 12,700 pounds of ammonia. Markers or tags identifying valves for the rooftop evaporator valve group, identified as EV-2, were missing. This condition exposed employees to an ammonia hazard.