Violation Detail
Standard Cited: 19100269 L08 V Electric Power Generation, Transmission, and Distribution.
This violation item has been deleted.
Inspection Nr: 1507500.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $13,653.00
Current Penalty: $0.00
Issuance Date: 05/28/2021
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 06/24/2021
Gravity: 10
Report ID: 0626300
Contest Date: 06/25/2021
Final Order: 04/01/2022
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/01/2022 | $0.00 | 06/24/2021 | Serious | |
Penalty | C: Contested | 07/09/2021 | $13,653.00 | 06/24/2021 | Serious | |
Penalty | Z: Issued | 05/28/2021 | $13,653.00 | 06/24/2021 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2: (a) On or about December 19, 2020, an employee working without wearing adequate protective clothing and other protective equipment when inspecting an electrical box with its cover opened was exposed to an electrical arc hazard.