Violation Detail
Standard Cited: 19100303 G01 I B General.
Inspection Nr: 1426374.015
Citation: 01004
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $5,205.00
Current Penalty: $4,600.00
Issuance Date: 01/27/2020
Nr Instances: 1
Nr Exposed: 10
Abatement Date:
Gravity: 1
Report ID: 0214200
Contest Date:
Final Order: 02/10/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/10/2020 | $4,600.00 | Serious | ||
| Penalty | Z: Issued | 01/27/2020 | $5,205.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(g)(1)(i)(B): The width of working space in front of the electric equipment shall be the width of the equipment or 762 mm (30 in.), whichever is greater. In all cases, the working space shall permit at least a 90-degree opening of equipment doors or hinged electrical panels. Location: 17 Madison Rd., Fairfield, NJ. a) Employer did not ensure that the working width in front of the electrical panel located in the production area was greater than 30 inches; on or about 8/27/19.