Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1420169.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,634.00
Current Penalty: $5,000.00
Issuance Date: 01/23/2020
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 02/28/2020
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 02/18/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/18/2020 | $5,000.00 | 02/28/2020 | Serious | |
Penalty | Z: Issued | 01/23/2020 | $7,634.00 | 01/29/2020 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a- Interior Lighting Panel #2A - 2039 Route 130 South, Florence NJ: The exterior of the circuit breaker box contained several unprotected openings and within the box unused openings, between circuit breakers, were not effectively closed. Condition observed on or about 12/11/18. IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.