Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1388059.015
Citation: 01004
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $7,293.00
Current Penalty: $1,000.00
Issuance Date: 05/21/2019
Nr Instances: 1
Nr Exposed: 1
Related Event Code (REC): R
Gravity: 5
Report ID: 0522000
Contest Date:
Final Order: 05/31/2019
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/31/2019 | $1,000.00 | Serious | ||
Penalty | Z: Issued | 05/21/2019 | $7,293.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means: a) On 3/26/2019 employees were exposed to electrical shock due to live wires of greater than 50 volts hanging from different electrical components such as, but not limited to the control instruments for a control panel located on the backside platform of the oven and a control sensor for the Co2 fire suppression system located under the backside of the oven platform.