Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1347436.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,293.00
Current Penalty: $5,105.10
Issuance Date: 02/20/2019
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 04/30/2019
Gravity: 5
Report ID: 0214500
Contest Date:
Final Order: 03/25/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/25/2019 | $5,105.10 | 04/30/2019 | Serious | |
Penalty | Z: Issued | 02/20/2019 | $7,293.00 | 03/18/2019 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: a) Pre-mix (Mezzanine Area): Electrical outlet boxes, disconnect switch boxes, pedestal fan, and control panels located in a Class II, Division I location, were not intrinsically safe, approved for a Class II, Division I, location, or safe for a Class II, Division I, location, on or about 9/19/18, 10/3/18, and 11/15/18. b) Silo Located Outdoors: Electrical motors and drive belts located in a Class II, Division I location, were not intrinsically safe, approved for a Class II, Division I, location, or safe for a Class II, Division I, location, on or about 11/15/18.