Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
Inspection Nr: 1331518.015
Citation: 01004
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/15/2019
Nr Instances: 2
Nr Exposed: 7
Abatement Date:
Gravity: 10
Report ID: 0316700
Contest Date:
Final Order: 02/11/2020
Related Event Code (REC): A
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | Z: Issued | 01/15/2019 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.106(e)(6)(ii): Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), were dispensed into containers without the nozzle and container are electrically interconnected: (a) BUILDING 350, PAINT KITCHEN - Employees used Sherwin Williams R91K00020 MIL-T-81772B T1 Polyurethane Reducer (Category 2 flammable liquid, flashpoint 37.4F, boiling point 172.4F) to flush and clean the pump after refilling the Tan paint tank, and the dispensing tube from the pump was not bonded to the small thinner pot that the reducer was circulated through and stored in, on or about July 19, 2018. (b) BUILDING 350, PAINT KITCHEN - Employees transferred Sherwin Williams R91K00020 MIL-T-81772B T1 Polyurethane Reducer (Category 2 flammable liquid, flashpoint 37.4F, boiling point 172.4F) to the small thinner pot using a diaphragm pump, and he dispensing tube from the pump was not bonded to the small thinner pot that the reducer was being transferred to, on or about July 19, 2018. No abatement certification or documentation required.
Translate