Violation Detail
Standard Cited: 19100269 L08 V Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1319790.015
Citation: 01004
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $12,934.00
Current Penalty: $3,000.00
Issuance Date: 08/29/2018
Nr Instances: 1
Nr Exposed: 3
Abatement Date:
Gravity:
Report ID: 0214200
Contest Date:
Final Order: 09/24/2018
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/24/2018 | $3,000.00 | Other | ||
| Penalty | Z: Issued | 08/29/2018 | $12,934.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm2: a) Kearny #12 gas compressor MCC Employees performing switching activities and troubleshooting of Siemens MCC with a supply line voltage of 4160 volts were not wearing Class 2 gloves, 4FR clothing and Switching hood, Class 4. Condition occurred on or about 5/29/2018