Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
Inspection Nr: 1305746.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,220.00
Current Penalty: $3,251.00
Issuance Date: 04/30/2018
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 06/04/2018
Gravity: 5
Report ID: 0522000
Contest Date:
Final Order: 05/22/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/22/2018 | $3,251.00 | 06/04/2018 | Serious | |
Penalty | Z: Issued | 04/30/2018 | $6,220.00 | 06/04/2018 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." The employer did not ensure that circuit breakers near Doors 15 and 16 which are used as switches for fluorescent lighting in the Production Area were listed and marked "SWD".