Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1295973.015
Citation: 01004
Citation Type: Serious
Abatement Status: Not Completed - Worksite Changed
Initial Penalty: $5,543.00
Current Penalty: $5,543.00
Issuance Date: 03/23/2018
Nr Instances: 3
Nr Exposed: 2
Abatement Date: 04/04/2018
Gravity: 1
Report ID: 0627500
Contest Date:
Final Order: 04/17/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 03/23/2018 | $5,543.00 | 04/04/2018 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(g)(1)(i)(A):The depth of the working space in the direction of access to live parts were not less than indicated in Table S-1. A minimum of three (3) ft. of clear working space is required to be maintained at Electric equipment 600 V or Less. In the warehouse: On or about February 28, 2018, the clear working space of 3-feet on electrical panel "A" (120-v/208-v) and panel "CR" (120-v/208-v) in the warehouse was not maintained. This condition exposed employees to fire and electrical shock hazards.