Violation Detail
Standard Cited: 19100303 G01 I C General.
Inspection Nr: 1287572.015
Citation: 01004
Citation Type: Serious
Abatement Date: 07/03/2018 2
Initial Penalty: $4,157.00
Current Penalty: $2,909.90
Issuance Date: 05/16/2018
Nr Instances: 2
Nr Exposed: 2
Related Event Code (REC):
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 06/12/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/12/2018 | $2,909.90 | 07/03/2018 | Serious | |
Penalty | Z: Issued | 05/16/2018 | $4,157.00 | 07/03/2018 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(g)(1)(i)(C): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, other equipment associated with the electric installation and located above or below the electric equipment extended more than 153 mm (6 inches) beyond the front of the equipment: IF Electrical Room: on, or about, January 11, 2018, transformers were installed in the working space in front of two General Electric panelboards, both labeled as LPA.