Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1225857.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $9,959.00
Current Penalty: $5,975.40
Issuance Date: 08/15/2017
Nr Instances: 5
Nr Exposed: 84
Abatement Date: 08/29/2017
Gravity: 5
Report ID: 0626600
Contest Date:
Final Order: 09/08/2017
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/08/2017 | $5,975.40 | 08/29/2017 | Serious | |
Penalty | Z: Issued | 08/15/2017 | $9,959.00 | 08/29/2017 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a. On or about April 18, 2017 at workstation #8 at merge conveyor #2 where an employee was exposed to an electrical hazard when using an electrical outlet box to power tools that had unused openings that were not effectively closed. b. On or about April 18, 2017 at workstation #10 at merge conveyor #2 where an employee was exposed to an electrical hazard when using an electrical outlet box to power tools that had unused openings that were not effectively closed. c. On or about April 18, 2017 at workstation #9 at merge conveyor #2 where an employee was exposed to an electrical hazard when using an electrical outlet box to power tools that had unused openings that were not effectively closed. d. On or about April 18, 2017 at the QC station control panel #1 that powers the merge conveyor where an employee was exposed to an electrical hazard that had unused openings that were not effectively closed. e. On or about April 18, 2017 at QC station control panel #2 that powers the merge conveyor where an employee was exposed to an electrical hazard that had unused openings that were not effectively closed.