Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1213058.015
Citation: 01004
Citation Type: Serious
Abatement Date: 06/23/2017 2
Initial Penalty: $10,864.00
Current Penalty: $6,600.00
Issuance Date: 05/08/2017
Nr Instances: 1
Nr Exposed: 150
Related Event Code (REC):
Gravity: 5
Report ID: 0418100
Contest Date:
Final Order: 05/17/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/17/2017 | $6,600.00 | 06/23/2017 | Serious | |
Penalty | Z: Issued | 05/08/2017 | $10,864.00 | 06/23/2017 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring and equipment not subject to deposits of combustible residues but located in a spraying area as herein defined were not explosion-proof type approved for Class I, group D locations and did not otherwise conform to the provisions of subpart S of this part, for Class I, Division 1, Hazardous Locations: 4321 Browns Bridge Road, Gainesville, GA - Employees are exposed to a fire hazard. Booths #1- #5 mixing areas, employees are required to mix flammable and combustible products (resin/gel coat) to spray paint cultured marble parts. Electrical equipment such as, but is not limited to lights, extension cords, a fan, and electrical outlets are located in the mixing areas. The electrical equipment was not approved for the location, on or about 01/12/17. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).