Violation Detail
Standard Cited: 19100333 B02 II B Selection and use of work practices
Inspection Nr: 1204162.015
Citation: 01004
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,926.00
Current Penalty: $4,000.00
Issuance Date: 06/26/2017
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 06/25/2018
Gravity: 5
Report ID: 0627500
Contest Date: 07/20/2017
Final Order: 06/25/2018
Related Event Code (REC): A;R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 06/25/2018 | $4,000.00 | 06/25/2018 | Serious | |
| Penalty | C: Contested | 08/07/2017 | $6,926.00 | 07/07/2017 | Serious | |
| Penalty | Z: Issued | 06/26/2017 | $6,926.00 | 07/07/2017 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.333(b)(2)(ii)(B): Control circuit devices, such as push buttons, selector switches, and interlocks, were used as the sole means for de-energizing circuits and equipment: At the substation: On or about January 19, 2017, the employer relied on the use of a selector switch as thee sole means for de-energizing VISTA distribution switchgear. The VISTA distribution switchgear was de-energized on the out-going side, but remained energized on the in-coming side.Employees were exposed to electrical hazards.