Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1201250.015
Citation: 01004
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $1,630.00
Current Penalty: $1,630.00
Issuance Date: 02/08/2017
Nr Instances: 1
Nr Exposed: 4
Abatement Date:
Gravity: 1
Report ID: 0111100
Contest Date:
Final Order: 03/08/2017
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 02/08/2017 | $1,630.00 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Panel 3 - The 480 volt panel used to energize the air compressor was blocked by a metal garbage can and not cleared to 36 inch working space.