Violation Detail
Standard Cited: 19100106 D04 III Flammable liquids.
Inspection Nr: 1192798.015
Citation: 01004
Citation Type: Serious
Abatement Date: 06/08/2017 2
Initial Penalty: $8,873.00
Current Penalty: $4,436.50
Issuance Date: 05/16/2017
Nr Instances: 1
Nr Exposed: 42
Related Event Code (REC):
Gravity: 10
Report ID: 0729700
Contest Date:
Final Order: 06/09/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/09/2017 | $4,436.50 | 06/08/2017 | Serious | |
Penalty | Z: Issued | 05/16/2017 | $8,873.00 | 06/08/2017 | Serious |
Text For Citation: 01 Item/Group: 004 Hazard:
29 CFR 1910.106(d)(4)(iii) Electrical wiring and equipment located in inside storage rooms used for Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 °F (37.8 °C), shall be approved under subpart S of this part for Class I, Division 2 Hazardous Locations; for Category 3 flammable liquids with a flashpoint at or above 100 °F (37.8 °C) and Category 4 flammable liquids, shall be approved for general use. The employer is failing to protect employees from fire and explosion hazards from flammable vapors. This was most recently documented on or about November 22nd, 2016 at the facility located at 1206 Illinois in Neodesha, Kansas, a non-intrinsically-safe portable fan was located in a flammable storage area and was turned on which resulted in a fire that injured an employee and destroyed much of the facility.